Current location of water allocations in the Burdekin Haughton Water Supply Scheme

A change to the location of a water allocation is possible between zones.

If the change can be made within the maximum and minimum constraints set by the trading rules then the change will generally be approved.

HIGH priority water allocations (ML)
BURDEKIN HAUGHTON WATER SUPPLY SCHEME Nominal Volumes as at COB 11th Nov 2024
Location Minimum Volume (ML) Current Volume (ML) Maximum Volume (ML) Projected Volume (ML) *
Burdekin Zone C 0 49,969 100,000 49,969
Burdekin Zone D 0 49,999 50,000 49,999
Burdekin Zone E 0 30 25,000 30
Haughton Zone A 0 0 8,800 0
Burdekin Zone A** 0 0 20,000 0
Burdekin Zone B** 0 0

All values in Megalitres

* This represents the forecasted “current volume” assuming all outstanding dealing certificates or matters under review are registered on the water allocations register.

** Burdekin Zone A and Burdekin Zone B are also known as the Lower Burdekin zone group when referenced in the water sharing rules for the Burdekin Haughton Water Supply Scheme.

A combined maximum or minimum volume for two or more zones means the total current volume for all those zones, when added together, must not breach that maximum or minimum figure. For example, if two zones have a combined maximum volume of 1,000ML then the current volume of both zones must always be at or below 1,000ML.

Some zones will also have individually specified maximum or minimum volumes as well as a combined maximum or minimum volume. For example, if Zone 1 and Zone 2 specify a maximum volume of 800ML and 950ML respectively, then the current volume for each zone must not exceed the volume specified for the zone value. If both these zones also have a combined maximum volume of 1,500ML then the current volume of both zones combined must not exceed 1,500ML.

MEDIUM priority water allocations (ML)
BURDEKIN HAUGHTON WATER SUPPLY SCHEME Nominal Volumes as at COB 11th Nov 2024
Location Minimum Volume (ML) Current Volume (ML) Maximum Volume (ML) Projected Volume (ML) *
Burdekin Zone C 524,892 620,402 850,000 620,402
Burdekin Zone D 0 0 25,000 0
Burdekin Zone E 0 0 75,000 0
Haughton Zone A 29,178 44,384 49,178 44,384
Burdekin Zone A** 267,944 279,681 350,000 279,681
Burdekin Zone B** 35,127 35,127

All values in Megalitres

* This represents the forecasted “current volume” assuming all outstanding dealing certificates or matters under review are registered on the water allocations register.

** Burdekin Zone A and Burdekin Zone B are also known as the Lower Burdekin zone group when referenced in the water sharing rules for the Burdekin Haughton Water Supply Scheme.

A combined maximum or minimum volume for two or more zones means the total current volume for all those zones, when added together, must not breach that maximum or minimum figure. For example, if two zones have a combined maximum volume of 1,000ML then the current volume of both zones must always be at or below 1,000ML.

Some zones will also have individually specified maximum or minimum volumes as well as a combined maximum or minimum volume. For example, if Zone 1 and Zone 2 specify a maximum volume of 800ML and 950ML respectively, then the current volume for each zone must not exceed the volume specified for the zone value. If both these zones also have a combined maximum volume of 1,500ML then the current volume of both zones combined must not exceed 1,500ML.